Skip to Content
Support
Brisk Air ConditionersNot heating but fan runs when Air conditioner is turned on
Brisk Air Conditioners

Brisk Air Conditioners

Not heating but fan runs when Air conditioner is turned on

Prova den här lösningen

Check the power source

a. If the air conditioner compressor or fan fails to operate, chances are it is not receiving power. Be sure the power cord is plugged in and no fuses or breakers are tripped.

b. The voltage reading should be taken at the unit power supply leads. One test should be performed when the unit is turned OFF and another with it running under load. If the voltage is not within the proper operating range, it must be corrected before trouble shooting of the unit can begin.

Check for proper AC volts at the connections at the units electronic control box.

c. If no voltage is present, the problem is in the coach wiring or breaker/fuse box. If voltage is present at the control box, proceed to verify voltage at the control box connection.

Behöver du mer hjälp?

Ställ en annan frågaBrisk Air Conditioners
Välj en annan produkt
Innehåll
Sitemap
SupportSupport & ServiceFrequently asked questionsWarrantyFind a dealer
Privacy PolicyCookie NoticeTerms & ConditionsTerms of Use